Here is what your AI co-agent found while you were away.
Monitoring 47 facilities - Last analysis: 6:12 AM
2.3M
Data points analyzed overnight
47
Facilities monitored
4
Findings require attention
Findings - Priority Ordered
CRITICAL ALARM
Booster Pump 4B - Alarm Pattern Anomaly Detected
ALARM INTELLIGENCE
ESCALATED: "Low Discharge Pressure" alarm fired at 11:47 PM last night. Night operator acknowledged in 4 seconds (typical for this alarm). But this time was different. Discharge pressure had been declining 2 psi/hour for the previous 6 hours before crossing the alarm threshold. This alarm has fired 312 times in the past year - average acknowledge time is 3.2 seconds. Operators treat it as noise. This is NOT noise.
Pattern analysis indicates early-stage cavitation or discharge check valve degradation. Suction pressure remained stable, ruling out supply issues. This matches the pattern from March 2025 that resulted in emergency pump replacement ($14,200 repair cost, 18 hours reduced capacity).
Recommended: Immediate investigation required. Check suction line for air leaks, inspect discharge check valve operation, verify impeller clearances. Do not dismiss this alarm as routine - the 6-hour pressure decline makes this actionable.
HIGH
Well Pump 7 Efficiency Decline
Discharge pressure dropped 8% over 12 days at constant speed. Runtime up 36%, production flat. Pattern consistent with impeller degradation or check valve obstruction.
Recommended: Operator should schedule a drawdown test and compare results to the last rehabilitation baseline.
WATCH
Effluent Ammonia Trending Toward Limit
Increased from 1.2 to 3.8 mg/L over 14 days. Permit limit: 5.0 mg/L. Estimated exceedance in 6-8 days at current rate. Correlated with 18% influent loading increase.
Recommended: Operator should increase aeration basin DO setpoint from 2.0 to 2.5 mg/L at the SCADA HMI. Monitor response over 48 hours.
INSIGHT
Energy Optimization Opportunity - Main St Boosters
61% of electricity costs occur during peak-rate hours across three booster stations. Estimated $34K annual savings available through pump scheduling adjustment and VFD optimization.
Recommended: Review VFD setpoint optimization with time-of-use rate shifting. Operator to adjust pump schedules at SCADA workstation.
Alarm Intelligence LEARNING FROM 312 ALARMS
The AI monitors every SCADA alarm and learns operator response patterns. When an alarm fires that looks like routine noise but is actually different from the pattern, it escalates to ensure operators investigate before acknowledging.
218
Alarms last 7 days
189
Routine (acknowledged <5 sec)
1
Escalated (anomaly detected)
Escalated Alarms Requiring Investigation
ESCALATEDFeb 6, 2026 11:47 PM
Booster Pump 4B - Low Discharge Pressure
This alarm has fired 312 times in the past year. Average operator acknowledge time: 3.2 seconds. Night operator acknowledged this instance in 4 seconds. But this time was different.
Why This Was Escalated:
Discharge pressure had been declining 2 psi/hour for 6 hours before crossing alarm threshold
Pattern does not match the 311 previous occurrences (which were momentary pressure dips)
Sustained pressure decline indicates equipment degradation, not transient condition
Similar pattern occurred March 2025 and resulted in emergency pump failure ($14,200 repair)
AI Recommendation:
Do not dismiss this alarm as routine. Investigate immediately: Check suction line for air leaks, inspect discharge check valve operation, verify impeller clearances. Early-stage cavitation or valve degradation likely.
Nuisance Alarm Candidates
These alarms fire frequently and are routinely acknowledged without investigation. Consider threshold adjustment or suppression.
Tank 7 - High Level Alarm
Fired 47 times (last 7 days)|Avg acknowledge: 2.1 seconds|0 investigations
AI Analysis: Alarm threshold set at 95% full. Tank reaches 94.8-95.2% daily during normal operations. Threshold should be raised to 96% or alarm should be suppressed as informational only.
AI Analysis: Residual drops below 0.2 mg/L threshold twice per shift during peak demand. Returns to normal within 5 minutes without operator intervention. Likely flow surge transient. Consider time-delay on alarm or adjust threshold to 0.15 mg/L.
Zone 4 - Low Pressure Alert
Fired 34 times (last 7 days)|Avg acknowledge: 2.9 seconds|2 investigations
AI Analysis: Triggers nightly between 2-4 AM when irrigation load drops and pressure control valve overshoots. Self-corrects within 3 minutes. Operators investigated twice but found no issue. Consider adding deadband to pressure control or suppress alarm during 2-4 AM window.
How Alarm Intelligence Works
Learns Normal:Tracks every alarm, operator acknowledge time, response actions, and outcomes over months
Identifies Noise:Alarms acknowledged in <5 seconds with no investigation = routine noise operators ignore
Detects Anomalies:When alarm looks like noise but data pattern is different, escalates with context
Recommends Fixes:Suggests threshold adjustments, suppression windows, or time-delays to eliminate nuisance alarms
Ask About Your Alarms
Have questions about alarm patterns, thresholds, or why something was escalated? Ask the AI analyst.
Why was the Pump 4B alarm escalated last night? We get that alarm all the time.
8:14 AM
ALARM ANALYST
Pump 4B Escalation Explanation
You are correct that "Low Discharge Pressure" at Pump 4B fires frequently - 312 times in the past year. Average operator acknowledge time is 3.2 seconds, which tells me operators treat it as routine noise.
But the instance at 11:47 PM last night was different:
Discharge pressure had been declining 2 psi/hour for 6 hours before crossing the alarm threshold
The 311 previous alarm instances were momentary pressure dips that self-corrected in under 30 seconds
A sustained 6-hour decline indicates equipment degradation, not a transient condition
I found a similar pattern in March 2025 that resulted in emergency pump failure ($14,200 repair cost)
The alarm itself looked routine, but the underlying data pattern was not. That is why I escalated it - to make sure an operator investigated before dismissing it as noise.
8:14 AM - Analysis completed in 1.8 seconds
Show me all the alarms at Booster Station 4 in the last 30 days. Which ones should I be worried about?
8:16 AM
ALARM ANALYST
Booster Station 4 - Alarm Summary (Last 30 Days)
I found 47 alarm events at Booster Station 4 in the past 30 days:
⚠️ Requires Attention (1 alarm)
Pump 4B Low Discharge Pressure - Escalated Feb 6 at 11:47 PM due to 6-hour declining trend (not typical pattern)
✓ Routine Noise (46 alarms)
Pump 4A VFD Communication Loss (12 times) - Momentary Modbus timeout, self-clears in 2-3 seconds
Station 4 High Pressure (16 times) - Pressure control valve overshoot during low-demand periods, self-corrects within 1 minute
My recommendation: The only alarm requiring attention is the Pump 4B escalation from last night. The other 46 alarms are routine operational transients. However, the "VFD Communication Loss" alarm firing 12 times in 30 days might indicate a Modbus wiring or termination issue worth investigating during scheduled maintenance.
8:16 AM - Analysis completed in 2.3 seconds
We get the Tank 7 high level alarm constantly. Should we just turn it off or raise the threshold?
8:18 AM
ALARM ANALYST
Tank 7 High Level Alarm - Threshold Analysis
I have been tracking Tank 7 high level alarm for the past 6 months. Here is what I see:
Current threshold: 95.0% full
Alarm frequency: 47 times in last 7 days (6.7 alarms per day)
Operator acknowledge time: avg 2.1 seconds (treated as noise)
Tank level during normal operations: 94.8% to 95.2% daily cycle
Actual overflow risk level: 98.5% full based on tank geometry and inlet flow rates
Recommendation: Raise Threshold to 96.5%
Do not disable the alarm entirely - tank overflow is a real operational risk. Instead, raise the threshold to 96.5%. This gives you:
Eliminates nuisance alarms during normal 94.8-95.2% cycling
Still provides 2% safety margin before actual overflow risk at 98.5%
Allows operators to respond when tank level is truly abnormal
Alternative option: If you want to keep the 95% threshold for informational purposes, change it to a "low priority" or "notification" alarm that does not require acknowledgment. Reserve "high priority" alarms for conditions that need immediate operator action.
8:18 AM - Analysis completed in 1.9 seconds
Auto-playing conversation...
Show alarms for Zone 4 last weekWhy do we get so many chlorine residual alarms?Which alarms should we suppress?Compare alarm patterns month over month
Well Pump 7 - Efficiency Analysis AI Analysis
Discharge Pressure (psi)
Runtime (hrs/day)
Historical Baseline
Decline Onset Detected - Jan 28
Discharge pressure began sustained decline from 57.8 psi baseline. Coincides with no operational changes in pump speed or well field configuration. Pattern flagged by Sentinel agent after 3 consecutive days of below-baseline readings.
Acceleration Point - Feb 3
Pressure decline rate doubled from 0.3 psi/day to 0.6 psi/day. Now 26% below historical baseline at comparable runtime. Confidence in impeller degradation increased from 45% to 68% based on pressure-flow curve deviation.
AI Analysis
Generated 6:12 AM
Discharge pressure has declined from 58.2 psi to 53.1 psi over the past 12 days while pump speed has remained constant at 1,780 RPM. Simultaneously, daily runtime has increased from 14.2 hours to 19.1 hours with no corresponding increase in total production volume.
Probable Causes (ranked by likelihood):
68%
confidence
Impeller Wear or Degradation
Pressure-flow curve shift is consistent with impeller erosion. Efficiency loss increases with flow rate, matching observed pattern.
22%
confidence
Check Valve Partial Obstruction
Would explain backflow reducing net production. Less likely given gradual onset rather than step change.
10%
confidence
Declining Well Level
Well drawdown data shows normal recovery rates (2.3 ft/hr). Static water level unchanged from last measurement.
Correlated Data
Power Consumption
+12% (358 > 401 kWh/day)
Well Drawdown Recovery
Normal (2.3 ft/hr)
Vibration Data
Not monitored
Last Maintenance
Sep 14, 2025
Impeller inspection, no issues found
Operator Action Required
The AI co-agent has identified this issue through data analysis only. All corrective actions must be performed by operations staff. The AI does not have write access to SCADA systems or operational controls.
1.
Schedule Drawdown Test
Operator should perform a drawdown test on Well Pump 7 at the wellhead and record results in OCore. Compare to September 2025 rehabilitation baseline.
2.
Check Pump Vibration
Field crew should collect vibration readings at the pump and motor bearings. The AI will compare these readings against baseline if entered into OCore.
3.
Inspect Check Valve
If drawdown test results are normal, inspect the discharge check valve for partial obstruction. Operator to isolate pump per LOTO procedures before inspection.
Once operator records test results in OCore, the AI will update its analysis and refine the probable cause assessment.
Effluent Ammonia - Compliance Trend Analysis AI Analysis
WATCH - PERMIT EXCEEDANCE PROJECTED IN 6-8 DAYS
Effluent Ammonia (mg/L)
Influent Loading (% of design)
Permit Limit (5.0 mg/L)
Projected Trajectory
Influent Correlation Detected - Jan 28
Influent loading began sustained increase from 82% to current 97% of design capacity. Seasonal pattern consistent with prior January-February periods. Ammonia rise rate correlates at 0.89 with influent loading change - strongly suggesting biological treatment capacity is being exceeded, not a process upset.
Rate Acceleration - Feb 2
Ammonia increase rate accelerated from 0.15 mg/L per day to 0.22 mg/L per day. Blower runtime and DO setpoints have not changed during this period. Without intervention, current trajectory projects permit exceedance (5.0 mg/L) between February 12-14.
AI Compliance Analysis
Generated 6:12 AM
Effluent ammonia has increased from 1.2 mg/L to 3.8 mg/L over 14 days. The current reading is 76% of the 5.0 mg/L permit limit. At the current rate of increase (0.22 mg/L/day over the last 5 days), the permit limit will be reached between February 12-14 without intervention.
Root Cause Assessment:
The ammonia increase correlates strongly (r=0.89) with rising influent loading, which has increased from 82% to 97% of design capacity over the same period. This is consistent with seasonal patterns observed in prior years. The biological treatment process is not keeping up with the higher nitrogen load because aeration capacity has not been adjusted to match.
Recommended Actions (priority-ordered):
Immediate - Today
I recommend the operator increase the aeration basin DO setpoint from 2.0 mg/L to 2.5 mg/L at the SCADA HMI. This provides additional dissolved oxygen for nitrifying bacteria to process the higher ammonia load. Expected response: ammonia reduction of 0.3-0.5 mg/L within 48 hours based on historical DO-response data for this facility.
48-Hour Follow-Up
If ammonia has not stabilized below 3.5 mg/L after 48 hours, consider increasing DO setpoint to 3.0 mg/L and bringing Blower 3 online for additional aeration capacity. The operator should make these changes at the SCADA HMI and set effluent ammonia sampling to 4-hour intervals during this period.
Planning - This Week
I recommend reviewing the seasonal aeration strategy with operations staff. Influent loading increases in January-February have caused similar ammonia trends in 2024 and 2025. Consider implementing a seasonal DO setpoint schedule at the SCADA system that proactively increases aeration capacity when influent loading exceeds 85% of design.
Current Readings
Effluent Ammonia
3.8 mg/L
76% of 5.0 mg/L permit limit
Days to Projected Exceedance
6-8 days
At current rate without intervention
Correlated Parameters
Influent Loading
97% of design (+18%)
Aeration DO Setpoint
2.0 mg/L (unchanged)
Blower Runtime
Blowers 1 & 2 at 92%
Blower 3 offline (available)
Mixed Liquor (MLSS)
3,400 mg/L (normal)
Water Temperature
12.4 C (seasonal low)
Lower temp reduces nitrification rate
Historical Pattern
Similar trend Jan-Feb 2025
Resolved with DO increase to 2.5
Compliance Impact if Permit is Exceeded
$25-50K
Potential penalty per exceedance event
Mandatory
State reporting within 24 hours
Possible
Consent order or enforcement action
Operator Workflow
I have increased the DO setpoint to 2.5 mg/L on Aeration Basin 1 at the SCADA HMI. Confirmed the blowers ramped up to match. What should I watch for over the next few hours?
7:14 AM
AI ANALYST
DO Setpoint Change Acknowledged - Monitoring Initiated
Good. I can see the DO reading in Basin 1 has started responding - currently reading 2.18 mg/L and climbing toward the new 2.5 mg/L setpoint. Here is what to watch for:
Next 2-4 Hours
DO should stabilize at or near 2.5 mg/L. If it plateaus below 2.3 mg/L, the blower may not have sufficient capacity and you may need to consider bringing Blower 3 online.
12-24 Hours
Ammonia should begin to flatten or decrease slightly. The nitrifying bacteria need time to respond to the additional oxygen. If ammonia continues rising at the same rate (0.22 mg/L/day), the DO increase alone may not be sufficient.
48 Hours
Target: effluent ammonia below 3.5 mg/L. Based on historical data, this facility has responded within 36-48 hours to DO increases of this magnitude during similar loading conditions.
I will continue monitoring the DO level, ammonia readings, and blower performance. I will alert you if ammonia does not begin responding within 18 hours or if DO fails to stabilize at the new setpoint. No further action is needed from you right now unless you want to adjust the monitoring interval.
Monitoring Schedule (automated alerts)
Every 4 hours: Ammonia trend check and DO stability verification
At 18 hours: First response assessment - will alert if no improvement detected
At 48 hours: Full summary with recommendation for next steps
7:14 AM - Monitoring schedule configured
If I need to bring Blower 3 online, are there any concerns with the electrical capacity or anything I should check first?
7:16 AM
AI ANALYST
Blower 3 Readiness Assessment
Good question. I reviewed the available operational data for Blower 3:
Last Run Date
Dec 18, 2025 (49 days ago)
Last Maintenance
Oct 2, 2025 (bearing service)
MCC Breaker Status
Unknown (not monitored by SCADA)
Rated Capacity
75 HP - same as Blowers 1 & 2
Before starting Blower 3, I recommend the operator check the following at the blower building:
Verify the MCC breaker for Blower 3 is in the ON position
Check the inlet filter for debris or blockage (49 days idle)
Confirm discharge valve is open and check valve is functioning
Start in manual mode first and verify airflow before switching to auto
Running all three blowers simultaneously should be within the electrical panel capacity based on the original design records, but I do not have real-time electrical metering data to confirm current loading. If the plant has a main switchgear power meter, it would be worth checking that total demand stays below the panel rating when Blower 3 starts.
7:16 AM - Assessment completed in 2.1 seconds
Auto-playing conversation...
AI Operations Analyst Reading from TimescaleDB - 2.3M data points (read-only)
How can I meet production targets but reduce energy costs at the three Main Street booster stations?
6:42 AM
AI ANALYST
Energy Analysis: Main Street Booster Stations 1, 2, 3
Analyzed 12 months of operational data (Jan 2025 - Jan 2026):
Monthly Energy Cost - Peak vs Off-Peak
Total electricity cost: $187,400 over 12 months
Peak-hour consumption: 61% of total cost ($114,300)
Average production: 4.2 MGD across three stations
Current efficiency: 1,480 kWh per million gallons
Recommendations
Consider shifting 30% of peak-hour pumping to off-peak using storage tank float optimization. The operator would adjust pump schedules at the SCADA workstation. Estimated savings: $34,300/year.
I recommend adjusting Station 2 VFD setpoint from 52 Hz to 48 Hz during low-demand periods (10 PM - 6 AM). This change should be made by the operator at the VFD controller or SCADA HMI. Estimated savings: $8,200/year.
Station 3 Pump B is operating 18% less efficiently than Pump A at comparable loads. I recommend designating Pump A as lead during peak hours in the pump scheduling configuration. Estimated savings: $4,100/year.
Total Estimated Savings: $46,600/year
Data sources: TimescaleDB power metering tags, SCADA pump status, utility rate schedule (Rocky Mountain Power TOU-8)
6:43 AM - Analysis completed in 4.2 seconds
What about Station 3 Pump B - is that an efficiency problem or a maintenance issue?
6:45 AM
AI ANALYST
Station 3 Pump B - Performance Comparison
Efficiency (kWh/MG) vs Flow Rate (GPM) - Pump A vs Pump B
Pump B is consuming 18% more energy than Pump A at comparable flow rates. The efficiency gap widens at higher flows (above 800 GPM), which suggests impeller wear rather than a controls issue. A controls problem would show consistent offset across all flow rates.
Pump B last maintenance: July 2025 (bearing replacement)
Pump B last impeller inspection: March 2024
Recommendation
I recommend scheduling a vibration analysis and impeller inspection. The field crew should perform these tests and record findings in OCore. If impeller replacement is needed, estimated cost is $3,200 for parts and labor vs. $4,100/year in excess energy cost. Payback period: 9.4 months.
6:45 AM - Analysis completed in 2.8 seconds
Create a maintenance task for Pump B impeller inspection and assign it to the field crew.
6:47 AM
AI ANALYST
Task Created: Station 3 Pump B - Impeller Inspection
Task IDWO-2026-0847PriorityMediumAssignedField Crew A - Morning ShiftLocationMain St Booster Station 3DueFeb 14, 2026EquipmentBST3-PUMP-B (Goulds 3196)
Scope of Work (auto-generated from analysis):
Perform vibration analysis on Pump B bearings and impeller assembly
Compare vibration spectrum to Pump A baseline for same flow conditions
Inspect impeller for erosion, pitting, or tip clearance wear
If impeller replacement needed: estimated $3,200 parts + labor (see attached analysis)
Record all measurements in OCore for AI trend tracking
Attached Context:
AI Efficiency Analysis (Feb 6)Pump Curve ComparisonGoulds 3196 Service Manual
Task created and assigned to Field Crew A. The energy analysis, pump performance comparison, and equipment manual are attached to the work order so the crew has full context when they perform the inspection. Once the crew records their findings in OCore, I will incorporate the results into the efficiency model for Station 3.
6:47 AM - Task created in 1.1 seconds
Can you build me a summary report of this energy analysis for the board meeting next Tuesday? Include the savings projections and the Pump B maintenance recommendation.
6:49 AM
AI ANALYST
Board Report: Main Street Booster Stations Energy Optimization
Report Preview
Energy Optimization Analysis - Main Street Booster Stations
Prepared February 6, 2026 | Data Period: January 2025 - January 2026
Executive Summary
AI-driven analysis of 12 months of operational data across Main Street Booster Stations 1, 2, and 3 identified $46,600 in annual energy savings through three operational adjustments. An additional equipment maintenance issue at Station 3 is contributing to $4,100/year in excess energy consumption and poses reliability risk if unaddressed.
$187,400
Annual Energy Cost
$46,600
Projected Annual Savings
24.9%
Cost Reduction
Recommended Actions
1. Operators optimize pump scheduling for off-peak rate periods ($34,300/yr)
2. Operators adjust Station 2 VFD setpoints during low-demand windows ($8,200/yr)
3. Designate Pump A as lead pump at Station 3 ($4,100/yr)
4. Field crew to perform Station 3 Pump B impeller inspection ($3,200 investment, 9.4-month payback)
Full report includes the trend charts, pump performance comparison scatter plot, month-by-month cost breakdown, and the maintenance work order for Pump B. All data is sourced from your TimescaleDB operational records with the analysis methodology documented. Want me to adjust anything before export?
6:49 AM - Report generated in 3.6 seconds
If we move forward with the pump scheduling changes, what order should we implement them in? And what should the operators watch for after making each change?
6:51 AM
AI ANALYST
Recommended Implementation Sequence and Monitoring Plan
Here is the sequence I would recommend. Each step should be implemented by the operator at the SCADA workstation, with a stabilization period before moving to the next change.
Week 1Designate Pump A as lead at Station 3
This is the lowest-risk change. The operator should update the lead/lag configuration in the pump controller or SCADA. No infrastructure changes required.
What to watch:
Verify Pump A starts first on demand calls for the first 48 hours
Confirm storage tank levels maintain target range during peak demand
Monitor Pump A runtime - it should not exceed 18 hrs/day to avoid premature wear
Week 2Adjust Station 2 VFD setpoint for off-peak
Operator should reduce VFD frequency from 52 Hz to 48 Hz during the 10 PM - 6 AM window. This can be configured as a time-based schedule in most VFD controllers or through the SCADA system.
Risks to monitor:
Pressure at the furthest service connection should stay above 35 psi minimum
Storage tank should not draw down more than 6 feet during off-peak reduced-speed operation
If pressure complaints come in from the service area, revert to 52 Hz and we can re-evaluate
Week 3-4Shift peak-hour pumping using storage optimization
This is the highest-impact change but requires adjusting storage tank float levels and pump start/stop setpoints. The operator should modify the high and low float setpoints to pre-fill tanks during off-peak hours (before 2 PM) and coast on stored water during peak rate hours (2 PM - 8 PM).
Critical checks:
Do not reduce storage below 50% capacity during peak demand periods
Fire flow requirements must be maintained at all times - verify with fire marshal if needed
Start with a 15% shift target for the first week, then increase to 30% after confirming system stability
After each step, I will track the energy metering data and compare against the baseline to measure actual savings vs. projections. I can generate a weekly comparison report so you can see the impact of each change before moving to the next one. All operational changes are made by you and your team - I will handle the data tracking and performance analysis.
Note: I have read-only access to SCADA and metering data. All setpoint changes, pump configurations, and VFD adjustments must be performed by the operator.
6:52 AM - Analysis completed in 3.4 seconds
How does our energy efficiency at these stations compare to industry benchmarks? Are we already doing well or are we behind?
6:54 AM
AI ANALYST
Energy Benchmarking: Main Street Boosters vs. Industry Standards
Energy Intensity Comparison (kWh per Million Gallons)
Your Main Street booster stations are currently at 1,480 kWh/MG, which places you in the bottom third of comparable booster installations according to AWWA benchmarking data for small-to-medium distribution systems (1-5 MGD).
AWWA top quartile for your system size: 1,050 kWh/MG
AWWA median: 1,250 kWh/MG
Your current performance: 1,480 kWh/MG (18% above median)
Projected after recommended changes: ~1,160 kWh/MG (7% below median)
The good news is that the recommended changes would move you from the bottom third to slightly better than median - a significant improvement without capital investment. To reach top-quartile performance, you would likely need VFD retrofits at Stations 1 and 3 (which currently have across-the-line starters) and possibly a storage tank capacity study to enable more aggressive off-peak pumping. That would be a separate capital planning conversation worth having with the board.
Want me to track progress?
After the operator implements each change, I can generate weekly benchmarking updates showing where you stand relative to AWWA targets. This gives you a clear before-and-after story for the board and helps validate the savings projections in real time.
Benchmark data: AWWA Energy Management for Water & Wastewater Utilities (2024 update). System size comparison: 1-5 MGD booster stations, western US utilities.
6:55 AM - Analysis completed in 4.1 seconds
Auto-playing conversation...
VFD retrofit ROIEscalated alarms analysisIdentify nuisance alarms3-year energy trendFind similar stations
AI Agent Settings
Configure how often your active AI agents run analysis and monitoring tasks. Sentinel agents run continuously on scheduled intervals. Analyst agents are available on-demand anytime.
Active Sentinel Agents
SCADA Alarm Intelligence & Prioritization
CRITICAL SAFETY
Monitors all SCADA alarms and operator response patterns. Learns which alarms are routinely acknowledged without investigation. Escalates critical alarms that deviate from normal patterns to prevent operators from missing dangerous conditions hidden in noise.
312 alarms monitoredActive1 escalation last 24h
Last 7 days: 218 alarms fired. 189 acknowledged in under 5 seconds (routine). 27 required investigation. 1 escalated due to anomalous pattern (Booster Pump 4B, Feb 6 11:47 PM). Learning: "Low Discharge Pressure" alarm at Booster 4B is typically nuisance, but 6-hour pressure decline before alarm threshold made this instance critical.
Equipment Performance Degradation Monitor
Analyzes pump efficiency, bearing vibration patterns, and runtime trends to predict maintenance needs 2-4 weeks before failure.
47 data sourcesActive
Compliance Boundary Monitor
Tracks effluent quality parameters against permit limits and alerts when trends approach regulatory boundaries.
12 data sourcesActive
Active Analyst Agents
Energy & Optimization Analyst
Answers operator questions about energy consumption, pump efficiency, VFD optimization, and time-of-use rate strategies.
On-demandActive
Analyst agents are available on-demand anytime through the AI Analyst interface. No scheduling configuration needed.
Browse pre-built AI agents designed for common water utility operational challenges. Subscribe to agents relevant to your operations - setup and configuration handled by OCore.
FEATURED
SCADA Alarm Intelligence & Prioritization
SENTINEL AGENT
Your SCADA system generates hundreds of alarms per week. Most get acknowledged in 3 seconds without investigation. The dangerous ones hide in the noise. This agent learns which alarms operators routinely ignore, identifies true emergencies that are different from the pattern, and escalates critical situations before they become failures. Solves alarm fatigue.
Monitors:All SCADA alarms, operator acknowledge patterns, response times, alarm frequency, nuisance alarm identificationDetects:Alarms acknowledged without action, repeated nuisance alarms, misconfigured thresholds, critical alarms buried in noiseEscalates:Alarms that deviate from normal patterns, equipment behavior changes, conditions operators may dismiss but shouldn'tExpected Benefit:Reduce alarm fatigue 60-80%, catch critical issues before failure, identify alarms that need threshold adjustments or suppressionSafety Impact:Prevents operators from missing critical alarms
The Alarm Fatigue Problem: Your operators see 200+ alarms per week. 85% are nuisance alarms acknowledged in seconds without investigation. When a truly critical alarm fires - pump cavitation, tank overflow risk, chemical feed failure - it looks exactly like the noise. This agent separates signal from noise and makes sure the critical ones cannot be missed.
Well Efficiency & Drawdown Monitor
SENTINEL AGENT
Monitors well production efficiency by analyzing runtime, production volume, and water level drawdown patterns. Detects declining well performance 2-4 weeks before critical issues develop.
Monitors:Well pump runtime, production volume, drawdown rates, specific capacity trendsExpected Benefit:Prevent emergency well failures, schedule planned rehabilitation, extend well life 2-5 yearsTypical Savings:$40K-80K per avoided emergency
Filter Performance & Backwash Optimizer
SENTINEL AGENT
Tracks filter run times, headloss development, turbidity breakthrough patterns, and backwash effectiveness. Identifies filters requiring media replacement or structural issues.
Monitors:Filter headloss, run time trends, turbidity patterns, backwash water usage, media condition indicatorsExpected Benefit:Optimize backwash timing, reduce water waste, extend media life, prevent compliance issuesTypical Savings:10-15% reduction in backwash water
Chemical Dosing & Cost Analyst
ANALYST AGENT
Analyzes chemical feed rates, treatment effectiveness, and cost per million gallons treated. Answers questions about optimization opportunities and alternative treatment strategies.
Analyzes:Chemical feed rates vs. production, treatment effectiveness, cost trends, dose optimizationExample Queries:"Can we reduce coagulant dosing without impacting turbidity?" "What is our chemical cost per MG vs. last year?"Typical Savings:5-12% reduction in chemical costs
Distribution System Leak Detection
SENTINEL AGENT
Detects anomalous flow patterns indicating potential leaks by analyzing night flow, zone pressure vs. consumption, and unexpected demand changes.
Monitors:Minimum night flow (MNF), zone meter discrepancies, pressure anomalies, consumption patternsExpected Benefit:Earlier leak detection, reduced water loss, faster response to main breaksTypical Savings:Recover 2-5% of non-revenue water
Asset Health & Maintenance Predictor
SENTINEL AGENT
Tracks equipment runtime hours, cycle counts, maintenance history, and performance trends to predict when assets will need service or replacement.
Monitors:Equipment runtime, maintenance intervals, performance degradation, failure patternsExpected Benefit:Transition from reactive to predictive maintenance, reduce emergency failures by 40-60%Typical Savings:$100K-300K annually
Multi-Permit Compliance Monitor
SENTINEL AGENT
Continuously monitors all operational parameters against drinking water and discharge permit limits. Alerts when trends approach boundaries, not just when they exceed.
Monitors:All permit parameters (MCLs, discharge limits), trend trajectories, seasonal patternsExpected Benefit:Prevent permit violations before they occur, maintain clean compliance recordAvoided Costs:$25K-100K per prevented violation
Need a custom agent for your specific operation?
Use the Agent Builder to design a custom AI agent tailored to your unique operational challenges. The OCore team will configure and deploy it specifically for your system.
Custom Agent Builder DESIGN YOUR AGENT
Build a custom AI agent tailored to your specific operational needs. This guided builder helps you define what patterns to monitor, what data sources to analyze, and what recommendations the agent should provide. All agents are read-only - they analyze data but never control systems.
Example: Distribution System Pressure Optimizer
SENTINEL AGENT
Monitors distribution system pressure zones continuously to identify opportunities for reducing energy consumption while maintaining minimum pressure requirements. Analyzes pressure readings across 47 monitoring points, correlates with pump station operations, and recommends pressure setpoint reductions when system-wide pressure exceeds minimum requirements by more than 15 psi.
Data Sources:
Pressure sensors (47 points), pump station flow and pressure, tank levels, VFD speeds
Monitoring Pattern:
Continuous analysis of pressure vs. minimum requirements, flagged when system-wide cushion exceeds 15 psi for 4+ hours
Recommendations:
Specific VFD setpoint reductions at identified pump stations, estimated energy savings, pressure safety margin verification
Expected Impact:
10-15% reduction in distribution pumping energy, $30-50K annual savings for mid-sized system
Build Your Custom Agent
Sentinel Agent
Continuous monitoring. Watches data patterns 24/7 and proactively alerts operators when conditions warrant attention. Best for predictive maintenance, efficiency monitoring, and compliance tracking.
Analyst Agent
On-demand analysis. Operator asks questions, agent analyzes data and provides answers with supporting evidence. Best for optimization studies, root cause investigation, and report generation.
Choose which SCADA tags and operational data the agent should analyze. The agent will have read-only access to this data.
Describe what patterns or conditions should trigger an alert. Be specific about thresholds, time windows, and what constitutes an actionable finding.
Describe what types of questions this agent should be able to answer. Provide example queries operators might ask.
What specific actions should the agent recommend? Remember: the agent analyzes and recommends, the operator reviews and executes.
Next steps: After submission, the OCore team will configure your custom agent using your specifications. Setup typically takes 2-3 weeks depending on data source complexity and baseline data collection requirements. You will receive a test deployment for validation before the agent goes into production monitoring.
AMI Data Enhancement Available
Leak detection works better with Advanced Metering Infrastructure
With AMI Data (Advanced)
Zone-level leak isolation
Individual service connection detection
Real-time usage anomalies
Location within 2-3 blocks
Without AMI Data (Standard)
System-wide minimum nightly demand analysis
Baseline night flow trend changes
Zone meter discrepancies
System-level detection (follow-up needed)
Your Current Setup
No AMI meter data detected. This agent will monitor system-wide minimum nightly demand and flag anomalous patterns. You will still get early leak detection, but isolation requires follow-up investigation.
AMI upgrade path: Deploy AMI meters later and this agent auto-upgrades to use that data. No reconfiguration needed.